Loading...
Ord 054-84 5/1/1984r ORDINANCE NO. 54-84 ORDINANCE AMENDING THE PLUMBING CODE OF THE CITY OF WICHITA FALLS, TEXAS, PROVIDING FOR THE REGU- LATION OF POTABLE WATER SUPPLY, PROVIDING FOR THE CONTROL OF CROSS-CONNECTION, BACKFLOW AND BACK- SIPHONAGE, AND ESTABLISHING THE CROSS-CONNECTION, BACKFLOW AND BACK-SIPHONAGE CONTROL BOARD. WHEREAS, the existence of cross-connections, backflow, and back-siphonage creates varying degrees of hazards to potable water within the water main and water supply systems and the City Council wishes to provide protections against such contamination while applying the principle that the degree of protection should be commensurate with the degree of hazard; and, WHEREAS, cross-connection, backflow and back-siphonage control requires the cooperation of the water distributors , public health officer, plumbing inspector, and the consumers , and the City Council desires to clearly set forth the responsibilities and duties of each. NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF WICHITA FALLS, TEXAS, THAT: SECTION 1 . Section 1204 of the Plumbing Code of the City of Wichita Falls is hereby amended to read as follows : SECTION 1204 . PROTECTION OF POTABLE WATER SUPPLY 1204 .1 -- BACKFLOW Every water outlet and the water distribution system shall be protected against backflow. The preferred method of protecting the water outlet from backflow shall be the method of having the outlet end from which the water flows spaced a distance above the flood- level rim of the receptacle into which the water flows, sufficient to provide a "minimum required air gap" as defined in American National Standard Institute A 112 .1. 2 . Where it is not possible to provide a minimum air gap, the water outlet shall be equipped with an accessibly located backflow preventer complying with Section 1204 .2 of this Code. 1204 . 2 -- APPROVAL OF DEVICES All devices for the prevention of backflow or back-siphonage shall meet the requirements of Table 505. Devices installed in a potable water supply for protection against backflow shall be main- tained in good working condition by the person or persons having control of such devices . The plumbing inspector, having jurisdiction, may inspect such devices, and if they are found to be defective or inoperative, shall require the replacement thereof. 1204 .3 -- WHERE REQUIRED (a) Flushometer. Flushometers shall be equipped with an approved vacuum breaker. The vacuum breaker shall be installed on the discharge side of the flushing vavle with the critical level at least four (4) inches above the overflow rim of the bowl . (b) Flushing Tanks. Flushing tanks shall be equipped with an approved ball-cock. The ball-cock shall be installed with the critical level of the vacuum breaker at least one (1) inch above the full opening of the overflow pipe. In cases where the ball-cock has no hush tube, the bottom of the water supply shall be installed at least one (1) inch above the full opening of the overflow pipe. (c) Lawn Sprinklers and Irrigation Piping Systems (1) Lawn sprinkler systems and irrigation piping systems shall be equipped with an approved backflow preventer to protect against contamination of the potable water system. The following devices shall be acceptable: Anti-siphon vacuum breakers, reduced pressure zone backflow preventers and double check type back pressure backflow preventers equipped with gate valves and test cocks . (2) Atmospheric type vacuum breakers shall be installed downstream of the last control valve, at least six (6) inches above the level of the highest sprinkler head. (3) All protective devices shall be installed in an accessible location to allow for inspection and maintenance and to isolate the sprinkler system from all other piping in the system. (d) Fixture Valve Outlets with Hose Attachments , Hose Bibbs and Lawn Hydrants . Fixture valve outlets with hose attachments , hose bibbs and lawn hydrants shall be protected by an approved back-siphonage backflow preventer or vacuum breaker on the discharge side of the valve . Back-siphonage backflow preventers may be installed directly on hose outlet connection threads . Vacuum breakers shall be installed at least six (6) inches above the highest point of usage. (e) Water Supply to Steam and Hot Water Heating Boilers , Heat Exchanges, etc . A backflow preventer device which will automatically vent to the atmosphere shall be installed in the water supply line to all steam and hot water space heating boilers, heat exchanges and similar devices, being supplied from the potable water system. Such devices shall prevent back-siphonage and backflow from the heating system into the potable supply lines , should the supply pressure fall below the pressure in the heating system. Such devices shall meet the requirements of Table 505, and nd shall bear such identifica- tion as is required by the applicable s tandard. 1204 . 4 -- BACKFLOW PREVENTER INSTALLATION Backflow preventers shall not be buried, and backflow preventers shall be so located as to prevent any relief openings from being submerged. When backflow preventers are installed in vaults or pits which extend below grade level, relief outlets shall be piped full size directly to the outside of the vault or pit, with piping terminating in a downward direction at a point not less than twelve (12) inches above grade. An opening shall be provided in the vault wall, at one-half the distance between the relief piping terminus and grade. This opening shall be at least four times the diameter of the relief outlet piping, or, if smaller openings are desired, they shall be not less than four in number, each being two and one- half (2-1/2) times the diameter of the relief outlet pipe. Sufficient clearance from the devices on all sides shall be provided to permit testing in place or removal for maintenance. Vault installations are not recommended and shall be avoided, except where necessary to protect the device from damage . In any case, vaults shall be so constructed and equipped with positive drain opening, as to prevent any part of the device from being submerged. 2 1204 . 5 -- GATE VALVES AND TEST COCKS REQUIRED All pressure type backflow preventers which are designed for periodic field testing after installation in the pipe line shall be equipped with gate valves on both the inlet and the outlet side of the backflow preventer. In addition, test cocks shall be provided and so located that test equipment, gauges, etc. , may be connected to device at such points that the pressure in each pressure zone may be detected and, in addition, a test cock shall be located upstream of the upstream gate valve or installed in a special tapping on the upstream side of the upstream gate valve. But, in any case, such test cock shall be accessibly located as close to the device as practical. Where applicable approved standards specify otherwise, the location of test cocks shall be as specified by the standard. SECTION 2 . Section 1205 , CROSS CONNECTION, BACKFLOW AND BACK- SIPHONAGE CONTROL, is hereby amended to read as follows : 1205 . CROSS CONNECTION, BACKFLOW AND BACK-SIPHONAGE CONTROL. 1205 .1 -- INTENT. (a) It is the intent of this section to recognize that there are varying degrees of hazard to potable water within the water main and water supply systems, and it is the intent to apply the principle that the degree of protection should be commensurate with the degree of hazard. (b) The ur ose of this section is : P P (1) To protect the public water main against actual or potential cross-connections, backflow and back-siphonage by isolating, within public property or private property, contamination or pollution that has occurred or may occur because of some undiscovered or unauthorized cross-connection on public property or private property. (2) To protect the water supply system within the public or private property against actual or potential cross-connections, backflow and back-siphonage by requiring such air gaps , vacuum breakers, backflow preventers, reduced pressure principle backflow preventers, and special devices as required by this section or other applicable regulations. (3) To eliminate cross-connections, backflow and back- siphonage of any other source of water or process water used for any purpose whatsoever which may jeopardize the safety of the water supply or which may endanger the health and welfare of the general public. (4) To establish a cross-connection, backflow and back- siphonage control program. (c) A cross-connection is defined as any physical connection or arrangement of pipes between two otherwise separate water supply systems, one of which contains potable water and the water, water of unknown or questionable safety, whereby water may flow from one system to the other, the direction of flow depending on pressure differential between the two systems. 1205. 2 -- DEFINITIONS In addition to the definitions contained in Chapter III of the Wichita Falls Plumbing Code, the following special definitions shall apply: BACK-SIPHONAGE BACKFLOW means a reversal of the normal direction of flow in the pipeline due to a negative pressure (vacuum) being created in the supply line with the backflow source subject to atmospheric pressure. 3 BACKFLOW PREVENTER means a device to prevent backflow. As there are two conditions of backflow, the device should be identified by the conditions which it is designed to prevent. (See Back Pressure Backflow Preventer, Backflow Preventer Reduced Pressure Type, Back-Siphonage Backflow Preventer) . BACK PRESSURE BACKFLOW PREVENTER means a device to prevent backflow due to a general condition in which the pressure in the system becomes greater than the supply pressure, the system being above atmospheric pressure . (See also Check Valves Assembly .) BACKFLOW PREVENTER, REDUCED PRESSURE TYPE means a device having dual check valves force-loaded, or biased, to a normally closed position, a chamber or zone between the check valves in which pressure is normally lower than the supply pressure, a relief or vent valve force loaded to a normally open position located in the zone to automatically open a passage between the zone and the atmosphere, should the zone pressure, for any reason, tend to equalize with or exceed the supply pressure . BACK-SIPHONAGE BACKFLOW PREVENTER, GENERAL means a device or a combination of devices for preventing back-siphonage in a water supply line. CHECK VALVES ASSEMBLY means a combination of spring and weight loaded check valves with resilient discs for the intended purpose of preventing back pressure backflow in a water supply line. Assembly is usually furnished with test cocks for field testing the tightness of the check valves . Some assemblies include a "Vacuum Breaker" to admit atmospheric air downstream of the assembly. CONSUMER means any person, firm or corporation using or receiving water from the City's water system CONTAMINANTS means any foreign material, solid or liquid, not common to the potable water supply which makes the water unfit or undesirable for human or animal consumption. CONTAMINATION means the admission of contaminants into the potable water supply . 1205 . 3 -- REGULATIONS (a) No water service connections to any premises shall be installed or maintained unless the potable water and water supply are protected against actual or potential contamination. (b) No cross connection shall be permitted to be made between any system of piping supplied by water from the main of the Public Utilities Department, and any other source of supply, either public or private, or any secondary supplies known to be unsafe for drinking water, such as shallow wells , reused industrial supplies, raw surface water or swimming pools . (c) Where City water is used as an auxiliary supply to a roof or suction tank, which is also supplied by water from any other source, such tank shall not be of the pressure type, but open. The delivery of City water shall be above the tank flow line and controlled by some type of automatic valve . 4 (d) It shall be unlawful to maintain storage tanks supplied only with City water, unless the tanks are satisfactorily built, and covered so as to prevent the entrance of contamination. They shall also be subject to periodical inspection by the Inspection Department, and maintained in a manner wholly satisfactory to the standards and requirements of the State Department of Health. Pumps taking suction from the City supply, serving such building storage, shall be installed or operated only upon permit from the Public Utilities Department, subject to their approval as to size, capacity and valving arrangements . (e) It shall be unlawful for anyone to interconnect private supplies, including deep well systems, with the Public Utilities Department water system. (f) Should any system supplied by City water be operated in violation of any provision of this article, it shall be the duty of the Public Utilities Department to completely disconnect all service lines serving such system until this section is properly complied with. Any cost of such disconnection and the estimated cost of reconnection must be paid by the consumer before service shall be restored. The Public Utilities Department shall not disconnect the water system unless the procedures set forth in Subsection 103 . 4 have been complied with by the plumbing inspector. 1205. 4 -- DUTIES AND RESPONSIBILITIES (a) The plumbing inspector shall enforce the provisions of this Code as to insure the potability of the consumer' s water system. The plumbing inspector has enforcement responsibility of new installation, alterations or repairs of water supply systems . He shall provide the Director of Public Utilities with the assistance required to enforce the provisions of this Section on existing water supply systems . (b) The Director of Public Utilities is responsible for the prevention of contamination and pollution of the public water mains. Such responsibility begins at the point of origin of the public water supply and includes adequate treatment facilities and water mains, and ends at the point of entrance to the consumer' s water system, provided adequate backflow and back-siphonage protection is maintained on all water supply systems directly connected to the City' s public system. (c) The consumer has the prime responsibility of preventing contaminants and pollutants from entering the water supply system and from entering the public water main or water source from his water supply system. The consumer shall protect his water supply system against actual or potential cross-connection, backflow or back-siphonage, as required by this Section, and other applicable regulations. He shall assure that all protective devices are tested and maintained in the work condition required. He shall assure the necessary plumbing permits are obtained for new water supply system repair to existing systems, as required by this Section. (d) In the event of contamination or pollution of a potable water system, the consumer shall notify immediately the plumbing inspector, the health officer or the Director of Public Utilities, in order that appropriate measures may be taken to overcome the contamination or pollution . 5 (e) The plumbing inspector, the health officer, the Director of Public Utilities, or their authorized representatives , shall have the right to enter any building, structure , or premises to perform any duty imposed upon them by the Plumbing Code or any other applicable City codes or State statutes . (f) Nothing herein shall relieve the consumer of the responsibility for conducting, or causing to be conducted, periodic surveys of water use practices on his premises to determine whether there are actual or potential cross-connections in the consumer' s water system through which contaminants or pollutants could flow back into a public water system or a potable consumer' s water system. (g) A Cross-Connection, Backflow and Back-Siphonage Control Board is hereby established. This Board shall assist the plumbing inspector, the Public Utilities Director, and the health officer in the enforcement of this Section and other applicable regulations. Complaints of any citizen shall be brought before the Board for review and recommendation to the City Council. The Board shall also serve as an appeals board in the manner as set forth in Section 1205 . 5. (h) It shall be the duty of the plumbing inspector, and the Director of Public Utilities to cause inspections to be made of all properties containing potable water systems and where cross- connections, backflow and back-siphonage is deemed possible. The frequency of inspections and reinspections based on potential health hazards involved shall be as established by the Cross-Connection, Backflow and Back-Siphonage Control Board. On request, the consumer shall furnish to the inspection agency any pertinent information regarding the water supply system on such property. (i) It shall be the duty of the Cross-Connection, Backflow and Back-Siphonage Control Board to establish the regulations required to prevent contamination and pollution of potable water. These regulations shall be uniform, taking into account the varying degrees of hazards for various premises , and shall properly utilize air gaps for preventive principles , devices, tests , maintenance and repair, as contained in ASSE Standards: No. 1001-70-Pipe, Applied Vacuum Breakers, Atmospheric Type; No. 1011-70-Hose Connection Type Vacuum Breakers; No. 1012-72 Breakers , Atmospheric Type, No. 1011-70 Hose Connection Type Vacuum Breakers, No . 1012-72 Backflow Preventers with Intermediate Atmospheric Vent; No. 1013-71 Reduced Pressure Principle Back Pressure Backflow Preventers, and No. 1015-73 , Double Check Valve Back Pressure Backflow Preventers, or as contained in AWWA Standard AWWA C506-79 , Backflow Prevention Devices--Reduced Pressure Principle and Double Check Valve Types or other approved testing agencies . (j ) The plumbing inspector, the Director of Public Utilities, or their authorized representatives, shall notify the consumer of the preventive actions required. The consumer has the right of appeal to the Board. 6 • 1205 . 5 -- THE CROSS-CONNECTION, BACKFLOW AND BACK-SIPHONAGE CONTROL BOARD. (a) The Wichita Falls Backflow and Back-Siphonage Control Board, hereinafter referred to as "the Board" shall be composed of the following: All members of the Plumbing Advisory Board, one member from the Public Utilities Department, one member from the Health Department, and one member from the Legal Department. (b) The Board shall select annually a chairman from among its members . The Board shall hold at least four regular meetings each year and such additional meetings as the chairman deems necessary. All hearings shall be held before not less than a majority of the Board . (c) In addition to the other duties set forth in this Section, the Board is hereby vested with the authority to decide appeals from any decision, ruling or determination of the plumbing inspector or health officer concerning control of cross-connections , backflow or back-siphonage . (d) Any person seeking a variance from the provisions of this Section or any person taking exception to and who is uniquely affected by any decision, ruling, requirement, rule, regulation or order of the plumbing inspector or the health officer concerning the control of cross-connections, backflow or back-siphonage, may appeal to the Board as established by this Section. Such appeals shall be made within fifteen (15) days after receiving notice of such decision, ruling, requirement, rule, regulation, or order by filing a written notice of appeal directly to the Board, specifying the ground thereof and the relief requested. Such an appeal shall act as a stay of the decision, ruling, requirement, rule, regulation or order in question until the Board has taken final action on the appeal, except when the plumbing inspector or health officer has deemed that the installation constitutes a hazard to human life, health, or welfare or which admit storm or groundwater to the sanitary sewer as provided by Section (103 .4) (a) . The Board, not less than thirty (30) days after the date of filing an appeal, shall set a date for the hearing and shall give notice thereof by registered mail to the interested parties . (e) Hearings before the Board shall be conducted in the following manner: (1) The Chairman of the Board shall act as the hearing examiner to conduct such hearings . (2) Any person making an appeal who is uniquely affected by the action of the plumbing inspector or health officer may appear in person or by agent or attorney and present evidence pertinent to the questions and issues involved and may examine and cross-examine witnesses . 7 (3) All testimony shall be under oath and recorded. The Board is authorized to have all the testimony transcribed and a transcript of such testimony, if transcribed, shall be made available to any party in the hearing upon payment of the normal fee, which shall not exceed the cost of transcribing such testimony (4) After giving due consideration to all evidence presented, the Board shall issue and enter such final order or make such final determination as it shall deem appropriate, and shall immediately notify the respondent thereof , in writing, by certified mail . Such order or determination shall be approved by at least a majority of the members of the Board. (5) Upon failure of the Board to enter a final order or determination within sixty (60) days after the final argument of any such eharing, the respondent shall be entitled to treat for all purposes such failure to act as a finding favorable to the respondent. 1205 .6 -- RECOMMENDED BACKFLOW PREVENTION Table 1200 is hereby adopted and incorporated into this code as recommended methods of backflow prevention. TABLE 1200 BACKFLOW PREVENTER GUIDE INSTALLATION RECOMMENDED Air Compressors Air Gap *Air Conditioning Reduced Pressure *Air Conditioned Chillwater Reduced Pressure *Air Conditioned Condenser Water . . . Reduced Pressure *Air Conditioned Cooling Towers Reduced Pressure Air Washers Air Gap Aspirator, Medical Atmospheric Vacuum Breaker Aspirator, Weedicide and Root Feeders . Hose Connection Vacuum Breaker Autoclave & Sterilizer Atmospheric Vacuum Breaker Autopsy Tables Atmospheric Vacuum Breaker Baptismal Fount Atmospheric Vacuum Breaker Bathtub Below Rim Filler Atmospheric Vacuum Breaker Bedpan Washer , Flushing Rim Atmospheric Vacuum Breaker Beverage Dispensing Machines Atmospheric Vacuum Breaker Bidet Atmospheric Vacuum Breaker Boiler, Industrial Feed Line Reduced Pressure Boiler, Residential Feed Line Atmospheric Vacuum Breaker Brine Tank Air Gap Bottle Washer Atmospheric Vacuum Breaker *Chemical Feeder Tanks Reduced Pressure Chiller Tanks Atmospheric Vacuum Breaker Chlorinator Atmospheric Vacuum Breaker Coffee Urn Atmospheric Vacuum Breaker Cooking Kettles Atmospheric Vacuum Breaker Condensate Tank Air Gap Cuspidor, Dental Atmospheric Vacuum Breaker Dairy Equipment Atmospheric Vacuum Breaker *Degreasing Equipment Reduced Pressure Detergent Dispenser Atmospheric Vacuum Breaker *Developing Tanks, Photo Atmospheric Vacuum Breaker Digesters, Hospital Reduced Pressure Dishwasher Atmospheric Vacuum Breaker 8 TABLE 1200 BACKFLOW PREVENTER GUIDE (Continued) INSTALLATION RECOMMENDED Drinking Fountain Air Gap *Dye Vats & Tanks Reduced Pressure Etchin g Tanks Reduced Pressure Fountain, Livestock Drinking Atmospheric Vacuum Breaker Fountain Ornamental Double Check Garbage Can Washer Atmospheric Vacuum Breaker Hose Faucets Hose Connection Vacuum Breaker Humidifier Tank & Boxes Atmospheric Vacuum Breaker Hydro-Therapy Baths Atmospheric Vacuum Breaker Irrigation System Atmospheric Vacuum Breaker Janitor Closets Hose Connection Vacuum Breaker Laundry Machine, Hospital Reduced Pressure Lavatory Air Gap Lawn Sprinkler Double Check Lawn Sprinkler, Chemical Injection. Reduced Pressure Main Line Reduced Pressure Make-Up Tank Atmospheric Vacuum Breaker Marina, Boat Connections Hose Connection Vacuum Breaker Pipette Washer Atmospheric Vacuum Breaker Photo Lab Sinks Atmospheric Vacuum Breaker Potato Peeler Air Gap *Processing Tanks Reduced Pressure Pump, Prime Lines Atmospheric Vacuum Breaker Pump, Water Oper Eject Atmospheric Bacuum Breaker Re-circulated Water Reduced Pressure Reclaim Pit Atmospheric Vacuum Breaker Serrated Faucets Double Check Valve with Intermediate Vacuum Breaker Sewer Flushing Manhole Atmospheric Vacuum Breaker Shampoo Basin Hose Rinse Atmospheric Vacuum Breaker or Intermediate Vacuum Breaker - Double Check Valve Sinks, Wash-up Air Gap Sitz Bath Atmospheric Vacuum Breaker Sizing Vats & Boxes Double Check Soap Mixing Tank Atmospheric Vacuum Breaker *Solution Tanks Reduced Pressure Sprinkler System, Fire Protection . Double Check Starch Tanks Double Check Steam Cleaner Connection Hose Connection Vacuum Breaker Steam Table Atmospheric Vacuum Breaker Stills Atmospheric Vacuum Breaker Swimming Pool, Commercial Double Check Telephone, Showers Hose Connection Vacuum Breaker Trap Primer Atmospheric Vacuum Breaker Ultrasonic Cleaner Atmospheric Vacuum Breaker Urinal, Trough Atmospheric Vacuum Breaker Wall Hydrants Hose Connection Vacuum Breaker Wall Hydrants , Frost Free Hose Connection Vacuum Breaker Water Softener, Commercial Reduced Pressure Water Treatment Tanks Double Check Water Well Secondary System Reduced Pressure *Selection is based on equipment using toxic chemical. If chemical is non-toxic, selection could be D.C .V. Assembly. 9 • HOSPITAL FIXTURES AND THEIR WATER SUPPLY PROTECTION _Fixtures Type of Protection* Remarks Aspirators : Laboratory Vacuum Breaker Portable Vacuum Breaker Vacuum System Vacuum Breaker Bedpan: Washers Vacuum Breaker Washer Hose Vacuum Breaker Locate 5 ft . above floor Boiling type sterilizer Air Gap Not less than twice the effective opening of the water supply Exhaust condenser Vacuum Breaker Flush floor drain Vacuum Breaker Locate 6 ft. above floor Hose connection Vacuum Breaker Pressure instrument Washer-sterilizer Vacuum Breaker Vacuum systems : Cleaning Air gap or vacuum breaker Fluid Suction Air gap or vacuum breaker *Where vacuum breakers are used, they shall be installed after the last control valve . Clinical, hydrotherapeutic and radiological equipment: All clinical hydrotherapeutic, radiological, or any equipment, whether mentioned or not, which is water supplied and/or discharges to the waste system, shall meet the requirements of this section and the code covering cross- connectors , air gaps, vacuum breakers, and check valves . Special equipment and devices found under these classes include those listed in Table G-4 .7 , Classes of Clinical , Hydrotherapeutic and Radiological Equipment . SECTION 3 . Table 505 in the Plumbing Code is hereby amended by adding to it the following: 10 L TABLE 505 - MATERIALS FOR PLUMBING INSTALLATION MATERIALS OTHER STANDARDS & REMARKS MISCELLANEOUS BACKFLOW ANSI PREVENTION A 112 .1 .2- Air Gap Standards 1973 Vacuum Breakers (Atmospheric ASSE 1001 - CSA B64 .1 .1 type) Vacuum Breakers ASSE 1001-1970 Water Closet Flush Tank Ball-cocks ASSE 1002-1977 Vacuum Breakers , Hose Bibb ASSE 1011-1970 - CSA B64 .2 Backflow Preventers with Intermediate Atmospheric Vent ASSE 1012-1972 - CSA B64 .3 Backflow Preventers reduced Pressure Principle ASSE 1013-1971 - May be used under constant line pressure - AWWA C506 - CSA B64 .4 Preventers, Double Check Valve ASSE 1015-1973 - AWWA C506 - CSA B64 .5 Lab . Faucets, Vacuum Breaker ASSE 1035 Reduced Pressure Zone ASSE AWWA USC or other Backflow Preventers approved agency Pressure Type ASSE 1020 - CSA B64 .1 .2 Vacuum Breaker USC Dual Check Valve Backflow Preventer ASSE 1124 - AWWA CA - USC Water Hammer Arresters ASSE 1010-1967 Water Heater, Electrical FS W-H-1961, residential 1-1971 Water heaters, gas , Volume I , ANSI AGA Approved automatic storage type water Z21 . 10 .1 heaters with inputs of 75, 000 1974 BTU per hour or less Water heaters, gas , Volume II ANSI AGA Approved circulating tank, instantaneous Z21 . 10 .3 and large automatic storage 1974 type water heaters Water Pressure Regulators ASSE Standard No . 1003 11 SECTION 4 . Subsection 1215 .6 , WATER HEATER OR BOILER OVER 200 , 000 BTU/HR INPUT is hereby added to the Plumbing Code and shall read as follows : 1215 .6 -- WATER HEATER OR BOILER OVER 100 ,000 BTU/HR INPUT. The installation of all water heaters and boilers 200 , 000 BTU/HR input and over shall comply with standards set forth by the Texas Department of Labor and Standards (Article 5221c, Vernon's Texas Civil Statutes) . SECTION 5 . Subsection 1215 .7, SAFETY PANS AND RELIEF VALVE WASTE is hereby added to the Plumbing Code and shall read as follows : 1215 .7 -- SAFETY PANS AND RELIEF VALVE WASTE . (a) When water heaters or hot water storage tanks are installed in such areas that leakage could cause water damage to the building or injury to the building occupants, the tank or heater shall rest in a high impact plastic pan of at least 60 mil (1/16 ") thickness or a galvanized steel or other metal pan of equal corrosive resistance, having a thickness at least equal to 24 gauge galvanized sheet steel . (b) Safety pans shall be no less than one and one-half (1-1/2) inches deep and shall be of sufficient size and shape to receive all drippings or condensate from the tank or heater and the discharge from the relief valve or valves . The pan shall be drained by an indirect waste pipe no less than one (1) inch in diameter or the diameter of the outlet of the required relief valve (s) , whichever is larger . (c) The pan drain shall extend full-size and terminate over a suitably located indirect waste receptor or floor drain or extend to the exterior of the building and terminate no less than six (6) inches or more than twenty-four (24) inches above grade . (d) When the discharge from the relief valve (s) is to be discharged into the safety pan, it shall be piped full-size of the valve outlet pipe size to a point no more than two (2) inches or no less than one (1) inch above the pan flood level rim. SECTION 6 . Subsection 1608, WATER HEATERS, is hereby amended by the addition of paragraph 1608 .2 (b) , which shall read as follows : (b) Where a water heater is elevated so that the top of the heater extends into an attic space, the top of the heater shall be enclosed by means of a tight bulk-head having the same cross-sectional area as the water heater closet. The door giving access to the gas burner shall not be higher than five feet, six inches (5 '6 ") above the floor. Where forced attic ventilation is used, adequate provisions shall be made against the possibility of back draft being induced through a water heater when such attic ventilation is in operation. SECTION 7 . Amend Section 1606 . AIR FOR COMBUSTION 1601 .1 -- VENTILATION REQUIREMENTS Rooms or spaces in which gas or liquid fuel burning appliances are installed shall be provided with minimum unobstructed combustion air openings as follows : One (1) square inch per one thousand (1, 000) BTU of unrestricted free area from an outside source . 12 PASSED AND APPROVED this the 1st day of May 1984 . A � ATTEST: ity Clerk 13 S Affidavit of Publication • THE STATE OF TEXAS COUNTY OF WICHITA (Paste Clipping Here) ORDINANCE NO.46-84 14 this 14 day of May ORDINANCE ACCEPTING IN- PROVEMENTS OF A PORTION OF THE 1982 CAPITAL IM- PROVEMENTS PROJECT NO. A.D 1984 personally appeared rsonall a ared before me,the undersigned authority 82-1 IN THE CITY OF WICHITA FALLS, TEXAS, AS DISIGNATED IN ORDINANCE NO. 87-82, Toni Belvedere bookkeeper DECLARING THE CONTRACT WITH ZACK BURKETT COM- PANY, WICHITA FALLS, TEXAS, FOR THE CONSTRUCTION OF for the Times Publishing Company of Wichita Falls, publishers of the Wichita Falls SAID IMPROVEMENTS, FULLY COMPLETED AND PERFORMED: DIRECTING THE ISSUANCE, EX- Record News, a newspaper published at Wichita Fails in Wichita County.Texas. and ECUTION AND DELIVERY OF CERTIFICATES IN EVIDENCE OF upon being duly sworn by me,on oath states that the attached,advertisement is a true SPECIAL.ASSESSMENTSA LEVIED AFTER GIVING -EFFECT TO and correct CO of advertising published In ONE(1) issues SUNDRY• CREDITS HEREIN copy g p AUTHORIZED AND ALLOWED AGAINST SOME OF SAID thereof on the following dates: ASSESSMENTS: DIRECTING THE CITY CLERK TO ENGROSS AND ENROLL THIS ORDINANCE BY May 14 COPYING THE CAPTION OF _ SAME IN THE MINUTE BOOK OF THE CITY COUNCIL OF THE CITY OF WICHITA FALLS,TEXAS,AND BY FILING THE COMPLETE ORDI- NANCE 9Zti ��fd—r/t -� IN APPROPRIATE ORDI- NANCE RECORDS OF SAID CITY: Bookkeeper for Times Publishing Company AND PROVIDING AN EFFECTIVE DATE of Wichita Falls ORDINANCE NO.i47-84 ORDINANCE WAIVING SEC- TIONS 4-15 AND 4-24 OF THE CODE OF ORDINANCES TO Subscribed and sworn to before me this the day and year first above written. ALLOE SALE OF BEER AT THE 1 CHILI COOK-OFF AT THE 4-H ) 1 UGHTHOUSE FOR THE BLIND N ORDINANCE NO 48-84y ;J�/ {. ORDINANCE WIAVING SEC- ,7 A TION 25-14 OF THE CODE OF jj// �/! ORDINANCE TO ALLOW A PUB- LIC DANCE AT THE 4-H BARN ON MIDWESTERN PARKWAY ,ORDINANCE NO.51-84 ORDINANCE NO.52-84 ORDINANCE NO.54-84 ON APRIL 28, 1984. AN ORDINANCE WAIVING OR- ORDINANCE WIAVING SEC- I ORDINANCE AMENDING THE ORDINANCE NO.49-84 DINANCES CONCERNING MU- TION 22-4 OF THE CODE OF PLUMBING CODE OF THE CITY AN ORDINANCE CLOSING, NICIPAL ENFORCEMENT OF ORDINANCES TO ALLOW P _ ING 'OF WICHITA FALLS, TEXAS, VACAATING, AND ABANDON- DEED RESTRICTIONS FOR LOT 5, SESSION AND CONSUMPTION PROVIDING FOR THE REGU- NG CERTAIN UTILITY EASE- BLOCK 11, SHEPPARD ESTATES OF ALCOHOLIC BEVERAGES IN LATION OF POTABLE WATER MENTS IN LOT N 2, BLOCK 18, (2400 PIEDMONT PLACE), HAMILTON PARK AND KIWANIS SUPPLY, PROVIDING FOR THE MIDWESTERN PARK SUB- WICHITA FALLS,TEXAS PARK ON JUNE 3, 1984 FOR CONTROL OF CROS-CONNEC- DIVISION, WICHITA FALLS, THE SYMPHONY CONCERT AND TION, BACKFLOW AND BACK- TEXAS ° .`''. DAVIS THE MAVERICK FEED HONOR- SIPHONAGE CONTROL BOAR ORDINANCE NO.50-84 ING THE SYMPHONY LEAGUE ORDINANCE NO.55-84 ORDINANCE MAKING AN AP- Notary Public, Texas r 7 ORDINANCE NO.53-84 ORDINANCE GRANTING TEM. PROPRIATION FROM THE REV- 1 `�- �° ORDINANCE AMENDING SEC- PORARY AUTHORITY TO STEVE COUNT T NUMBERS FUND TO AC- My Commission Expire s _y TION 25-22 OF THE CODE OF KNUDSEN,DOING BUSINESS AS COUNT NUMBERS LISTED ;,4i ._;`- ORDINANCES OF THE CITY OF PRESTIGE LIMOUSINE,TOOPER• BELOW, AND DECLARING AN n:+aaa WICHITA FALLS TO ALLOW ATE A LIMOUSINE SERVICE ENERGENCY DANCE HALLS TO REMAIN OPEN 'WITHIN THE CORPORATE!) ORDINANCE NO.51-84^e ON SUNDAYS. BOUNDARIES OF THE CITY OF WICHITA FALLS